emcp/backend/tests/test_modbus_client.py

296 lines
12 KiB
Python

from __future__ import annotations
from datetime import datetime
from typing import Dict, List, Sequence, Tuple
from app.adapters.device_client import (
AI_ALARM_START_REGISTER,
AI_CHANNEL_START_REGISTER,
AI_INPUT_COUNT,
AI_INPUT_START_REGISTER,
AO_CHANNEL_START_REGISTER,
CDeviceClient,
DI_INPUT_REGISTER,
DO_INPUT_REGISTER,
DO_STATE_REGISTER,
EVENT_FLAG_REGISTER,
EVENT_INPUT_START_REGISTER,
EVENT_SUCCESS_REPLY_REGISTER,
LINE_ALARM_REGISTERS_PER_LINE,
LINE_ALARM_START_REGISTER,
LINE_START_REGISTERS,
ModbusTransport,
TIME_SYNC_START_REGISTER,
UART_CONFIG_REGISTER_COUNT,
UART_CONFIG_START_REGISTER,
VALUE_GROUP_FIELDS,
)
from app.schemas.platform import (
AiAlarmSettingIn,
AlarmRule,
ChannelConfigIn,
ChannelItem,
DeviceConfigIn,
LineAlarmSettingIn,
NetConfigItem,
SoftwareVersion,
HardwareVersion,
SwitchControlIn,
SystemConfigIn,
TimeSyncConfigIn,
UartConfigItem,
)
class FakeTransport(ModbusTransport):
def __init__(self) -> None:
self.input_registers: Dict[int, int] = {}
self.holding_registers: Dict[int, int] = {}
self.discrete_inputs: Dict[int, bool] = {}
self.coils: Dict[int, bool] = {}
self.written_registers: List[Tuple[int, List[int]]] = []
self.written_coils: List[Tuple[int, bool]] = []
def set_input_block(self, address: int, values: Sequence[int]) -> None:
for offset, value in enumerate(values):
self.input_registers[address + offset] = int(value)
def set_holding_block(self, address: int, values: Sequence[int]) -> None:
for offset, value in enumerate(values):
self.holding_registers[address + offset] = int(value)
def set_discrete_block(self, address: int, values: Sequence[bool]) -> None:
for offset, value in enumerate(values):
self.discrete_inputs[address + offset] = bool(value)
def set_coil_block(self, address: int, values: Sequence[bool]) -> None:
for offset, value in enumerate(values):
self.coils[address + offset] = bool(value)
def read_input_registers(self, address: int, count: int) -> List[int]:
return [self.input_registers.get(address + offset, 0) for offset in range(count)]
def read_holding_registers(self, address: int, count: int) -> List[int]:
return [self.holding_registers.get(address + offset, 0) for offset in range(count)]
def read_discrete_inputs(self, address: int, count: int) -> List[bool]:
return [self.discrete_inputs.get(address + offset, False) for offset in range(count)]
def read_coils(self, address: int, count: int) -> List[bool]:
return [self.coils.get(address + offset, False) for offset in range(count)]
def write_registers(self, address: int, values: Sequence[int]) -> None:
block = [int(value) for value in values]
self.written_registers.append((address, block))
for offset, value in enumerate(block):
self.holding_registers[address + offset] = value
def write_coil(self, address: int, value: bool) -> None:
self.written_coils.append((address, bool(value)))
self.coils[address] = bool(value)
def test_modbus_client_reads_upstream_data() -> None:
transport = FakeTransport()
client = CDeviceClient(transport=transport)
for line_index, start_register in enumerate(LINE_START_REGISTERS, start=1):
values: List[int] = []
base = float(line_index * 100)
for field_offset, _field_name in enumerate(VALUE_GROUP_FIELDS, start=1):
values.extend(client._float_to_registers(base + field_offset))
transport.set_input_block(start_register, values)
ai_values: List[int] = []
for index in range(AI_INPUT_COUNT):
ai_values.extend(client._float_to_registers(1.25 + index))
transport.set_input_block(AI_INPUT_START_REGISTER, ai_values)
transport.set_discrete_block(0x0000, [True, False, True, False, True, False, True, False, True, False, True, False])
transport.set_input_block(DO_INPUT_REGISTER, [0x0AAA])
transport.set_input_block(DI_INPUT_REGISTER, [0x0555])
realtime = client.read_realtime_data()
assert len(realtime.line_list) == 4
assert realtime.line_list[0].sec_val.Ua == 101.0
assert realtime.line_list[1].sec_val.Pt == 210.0
assert realtime.line_list[3].sec_val.frq == 426.0
assert realtime.ai_collect["ai1"] == 1.25
assert realtime.ai_collect["ai8"] == 8.25
assert realtime.ai_collect["ai9"] == 0.0
assert realtime.switch["di1"] == 1
assert realtime.switch["di2"] == 0
assert realtime.switch["do1"] == 0
assert realtime.switch["do2"] == 1
def test_modbus_client_reads_alarm_event_once() -> None:
transport = FakeTransport()
client = CDeviceClient(transport=transport)
timestamp = int(datetime(2026, 5, 25, 12, 0, 0).timestamp())
transport.set_input_block(EVENT_FLAG_REGISTER, [1])
transport.set_input_block(
EVENT_INPUT_START_REGISTER,
[
timestamp & 0xFFFF,
(timestamp >> 16) & 0xFFFF,
123,
(2 << 12) | (1 << 8) | 1,
456,
],
)
alarms = client.read_alarm_events()
duplicate = client.read_alarm_events()
assert len(alarms) == 1
assert alarms[0].no == "2"
assert alarms[0].type == "PT断线"
assert "线路2PT断线" in alarms[0].content
assert duplicate == []
assert transport.written_registers[-1] == (EVENT_SUCCESS_REPLY_REGISTER, [1])
def test_modbus_client_reads_and_writes_downstream_registers() -> None:
transport = FakeTransport()
client = CDeviceClient(transport=transport)
ai_channel_payload = client._bytes_to_registers(
bytes(
[
0, 1, 0, 20, 0,
1, 2, 7, 8, 1,
]
+ [0] * 50
)
)
ao_channel_payload = client._bytes_to_registers(
bytes(
[
1, 1, 6, 10, 2,
]
+ [0] * 55
)
)
line_alarm_payload_bytes = bytes(
[
180, 5, 1, 1,
200, 6, 2, 0,
20, 7, 3, 1,
30, 8, 4, 0,
50, 9, 5, 1,
0, 10, 6, 1,
0, 11, 7, 0,
]
) + (10).to_bytes(2, "big") + (20).to_bytes(2, "big")
ai_alarm_payload_bytes = bytes(
[
20, 0, 3, 1, 1,
]
+ [0] * 55
)
timestamp = int(datetime(2026, 5, 25, 12, 34, 56).timestamp())
transport.set_holding_block(AI_CHANNEL_START_REGISTER, ai_channel_payload)
transport.set_holding_block(AO_CHANNEL_START_REGISTER, ao_channel_payload)
transport.set_holding_block(
LINE_ALARM_START_REGISTER + LINE_ALARM_REGISTERS_PER_LINE,
client._bytes_to_registers(line_alarm_payload_bytes),
)
transport.set_holding_block(AI_ALARM_START_REGISTER, client._bytes_to_registers(ai_alarm_payload_bytes))
transport.set_holding_block(TIME_SYNC_START_REGISTER, [timestamp & 0xFFFF, (timestamp >> 16) & 0xFFFF])
device_payload = DeviceConfigIn(
password="",
hardware_version=HardwareVersion(),
software_version=SoftwareVersion(),
net=[NetConfigItem(nic="网卡一", ip="192.168.1.10", mask="255.255.255.0", gateway="192.168.1.1", protocol="Modbus TCP")],
uart=[
UartConfigItem(port="COM1", baud=9600, parity="NONE", data_bits=8, stop_bits=1, protocol="Modbus RTU"),
UartConfigItem(port="COM2", baud=115200, parity="EVEN", data_bits=8, stop_bits=2, protocol="Modbus RTU"),
],
)
channel_payload = ChannelConfigIn(
ai_channel=[ChannelItem(ch=1, singal_type="4-20mA", line_no=1, type="UA", limit_low=0, limit_high=20)],
ao_channel=[ChannelItem(ch=2, singal_type="1~5V", line_no=2, type="Q", limit_low=1, limit_high=8)],
)
line_alarm_payload = LineAlarmSettingIn(
line_no=2,
over_limit_alarm=[
AlarmRule(category="电压", limit=180, delay=5, output_node="开出1", enabled=True),
AlarmRule(category="电流", limit=200, delay=6, output_node="开出2", enabled=False),
AlarmRule(category="差流", limit=20, delay=7, output_node="开出3", enabled=True),
AlarmRule(category="功率", limit=30, delay=8, output_node="开出4", enabled=False),
AlarmRule(category="频率", limit=50, delay=9, output_node="开出5", enabled=True),
],
fault_alarm=[
AlarmRule(category="PT断线", delay=10, output_node="开出6", enabled=True),
AlarmRule(category="CT断线", delay=11, output_node="开出7", enabled=False),
],
)
ai_alarm_payload = [
AiAlarmSettingIn(
channel_no=1,
singal_type="4-20mA",
limit_low=0,
limit_high=20,
delay=3,
output_node="开出1",
enabled=True,
).model_dump()
]
system_payload = SystemConfigIn(time_sync="2026-05-25 12:34:56", brightness=80, screen_saver=60)
switch_payload = SwitchControlIn(ch=3, action=1)
read_channel = client.read_channel_config()
read_line_alarm = client.read_line_alarm_setting(2)
read_ai_alarm = client.read_ai_alarm_setting()
read_system = client.read_system_config()
read_time_sync = client.read_time_sync_config()
device_result = client.send_device_config(device_payload)
channel_result = client.send_channel_config(channel_payload)
line_result = client.send_line_alarm_setting(line_alarm_payload)
ai_alarm_result = client.send_ai_alarm_setting(ai_alarm_payload)
system_result = client.send_system_config(system_payload)
time_sync_result = client.send_time_sync_config(TimeSyncConfigIn(time_sync="2026-05-25 13:45:00"))
control_result = client.send_switch_control(switch_payload)
register_map = {address: values for address, values in transport.written_registers}
assert UART_CONFIG_START_REGISTER in register_map
assert len(register_map[UART_CONFIG_START_REGISTER]) == UART_CONFIG_REGISTER_COUNT
assert read_channel["ai_channel"][0]["singal_type"] == "4-20mA"
assert read_channel["ao_channel"][0]["type"] == "P"
assert read_line_alarm["line_no"] == 2
assert read_line_alarm["transformer_change"][0]["value"] == 10.0
assert read_line_alarm["transformer_change"][1]["value"] == 20.0
assert read_ai_alarm[0]["channel_no"] == 1
assert read_ai_alarm[0]["delay"] == 3
assert read_system["time_sync"] == "2026-05-25 12:34:56"
assert read_time_sync["time_sync"] == "2026-05-25 12:34:56"
assert AI_CHANNEL_START_REGISTER in register_map
assert len(register_map[AI_CHANNEL_START_REGISTER]) == 30
assert AO_CHANNEL_START_REGISTER in register_map
assert len(register_map[AO_CHANNEL_START_REGISTER]) == 30
assert LINE_ALARM_START_REGISTER + LINE_ALARM_REGISTERS_PER_LINE in register_map
assert len(register_map[LINE_ALARM_START_REGISTER + LINE_ALARM_REGISTERS_PER_LINE]) == 16
assert AI_ALARM_START_REGISTER in register_map
assert len(register_map[AI_ALARM_START_REGISTER]) == 30
assert TIME_SYNC_START_REGISTER in register_map
assert len(register_map[TIME_SYNC_START_REGISTER]) == 2
assert DO_STATE_REGISTER in register_map
assert register_map[DO_STATE_REGISTER][0] == 0b100
assert transport.written_coils == [(2, True)]
assert device_result["send_status"] == "成功"
assert channel_result["modbus_written"]["ai_registers"] == 30
assert line_result["line_no"] == 2
assert ai_alarm_result["items"] == 1
assert system_result["send_status"] == "成功"
assert "brightness" in system_result["ignored_fields"]
assert time_sync_result["target"] == "time_sync"
assert time_sync_result["time_sync"] == "2026-05-25 13:45:00"
assert "执行成功" in control_result["control_status"]